Pfannenberg - Outdoor Cooling Units DTS 3165 & DTS 3185

Description

Cooling units 1948 W
 
  • particularly suitable for the food industry and outdoor applications high protection system IP 56, maintenance-free
  • NEMA 3R/4 (DTS 3165) unit with powder coated steel cover
  • NEMA 4/4X (DTS 3185) unit with stainless steel cover
  • condenser with 3 mm fin spacing, highly effective protection against strongly contaminated ambient air
  • large distance between intake and exhaust vents, safe circulation within the electrical enclosure due to long passage of air, therefore hot spots are eliminated
  • integrated condensate evaporation system

Technical Information

Data DTS 3165 (NEMA 3R/4) DTS 3185 (NEMA 4/4X)
Rated voltage ±10 % AC 50/60 Hz
400 / 460 V 3~ 230 V 400 / 460 V 3~ 230 V
Cooling capacity
according to EN 14511
A35/A35 1948 W
A35/A50 1045 W
Ambient temperature SC 0 … +55 °C / +32 … +131 °F
LAP –40 … +55 °C / –40 … +131 °F
Degrees of protection
according to NEMA
3R/4 towards the electrical enclosure if
used as intended by the manufacturer
4/4X towards the electrical enclosure if used as intended by the manufacturer
Condensate management integrated condensate evaporation system with safety overflow
 

Further technical details and dimensions can be found in the download section on this page under product sheet.

 
Ordering details DTS 3165 DTS 3185
Type Rated voltage 400/460 V AC 230 V AC 400/460 V AC 230 V AC
Standard Controller Article number 13383636355 13383639355 13383636158 13383639158
LAP ¹ Article number 13383636375 13383639375 13383636178 13383639178
 
 
 

LAP (Low Ambient Package): includes 900 W enclosure heater and a thermostat to be placed inside the enclosure.

DTS 3165 (NEMA 3R_4), DTS 3185 (NEMA 4_4X) COOLING UNITS 1948–2050 W
  Download